AK-CH
650
Capacity
controller RS8ER302 © Danfoss 2016-02
37
12
Supply voltage
Supply voltage is only connected to the controller module. The
supply to the other modules is transmitted via the plug between
the modules. The supply must be 24 V +/-20%. One transformer
must be used for each controller. The transformer must be a class
II. The 24 V must not be shared by other controllers or units. The
analog inputs and outputs are not galvanically separated from the
supply.
The + and – 24V input must not be earthed.
Transformer size
The power consumption grows with the number of modules used:
Module
Type
Number á
Effect
Controller
1 x 8 =
8 VA
Extension module
200-series
_ x 5 =
__ VA
Extension module
100-series
_ x 2 =
__ VA
Total
___
VA
Example continued:
Controller module
8 VA
+ 1 extension module in 200-series 5 VA
+ 1 extension module in 100-series
2 VA
------
Transformer size (least)
15 VA
Common pressure transmitter
If several controllers receive a signal from the same pressure trans-
mitter, the supply to the affected controllers must be wired so that
it is not possible to switch off one of the controllers without also
switching off the others. (If one controller is switched off, the sig-
nal will be pulled down, and all the other controllers will receive a
signal which is too low)