64
Capacity
controller RS8ER302 © Danfoss 2016-02
AK-CH
650
Set alarm priorities
1. Go to Configuration menu
2. Select Alarm priorities
3. Set priorities for Suction group
Press the +-button to go on to the next page
4. Set alarm priorities for condenser
Press the +-button to go on to the next page
Very many functions have an alarm connected.
Your choice of functions and settings has connected all the relevant
alarms that are current. They will be shown with text in the three
pictures.
All alarms that can occur can be set for a given order of priority:
• ”High” is the most important one
• ”Log only” has lowest priority
• ”Disconnected” gives no action
The interdependence between setting and action can be seen in the
table.
Configuration - continued
.
The first alarms for the suction groups are shown here.
Further down in the display the priorities for the compressors’ safety
circuits are set.
In our example we select the settings shown here in the display
Setting
Log
Alarm relays selection
Net-
work
AKM-
dest.
Non
High
Low - High
High
X
X
X
X
1
Medium
X
X
X
2
Low
X
X
X
3
Log only
X
Discon-
nected
See also alarm text