Schedule function
1. Go to Configuration menu
2. Select schedule
3. Setup schedule
Before regulation is started we will set the schedule function for the
night setback of the suction pressure.
In other cases where the controller is installed in a network with one
system unit, this setting may be made in the system unit which will then
transmit a day/night signal to the controller.
Press a weekday and set the time for the day period.
Continue with the other days.
A complete weekly sequence is shown in the display.