26.04.2005
Configuration & control of the AC SuperDrive
In order to generate an Open Drain Output voltage that is equal to the Dc Bus Voltage, the Pull
Time is set to zero and the Hold Voltage is set to a voltage that always is above the Dc Bus
Voltage (for example, 10000 centiV in a 48 V system).
6.13.1 P
ARAMETERS
The parameters and variables for the Open Drain Output Control are summarized in the following
table.
Index
Sub-
Index
Name
Description
2020h
2
Open Drain Output 1
Mode
Pin 2 in K1.
1 = Main contactor
2 = General output
2020h
3
Open Drain Output 2
Mode
Pin 10 in K1.
1 = Main contactor
2 = General output
2060h
2
Open Drain Output 1 :
Pull Time
During this time in ms the Pull Voltage is generated.
2060h
3
Open Drain Output 1 :
Pull Voltage
Initial voltage in centiV between B+ and output (Pin 2
in K1) when output is enabled.
2060h
4
Open Drain Output 1 :
Hold Voltage
Voltage in centiV that follows upon the Pull Voltage.
2061h
2
Open Drain Output 2 :
Pull Time
During this time in ms the Pull Voltage is generated.
2061h
3
Open Drain Output 2 :
Pull Voltage
Initial voltage in centiV between B+ and output (Pin 10
in K1) when output is enabled.
2061h
4
Open Drain Output 2 :
Hold Voltage
Voltage in centiV that follows upon the Pull Voltage.
2062h
2
Current
Total current in mA through the Open Darin Outputs.
2062
3
Switching Frequency
Open Drain Outputs Switching Frequency (1, 2, 4, 8 or
16 kHz)
Table 25. Open Drain Output Control – Parameters and Variables.
User's Guide 1.0
Item No.
89Y05120A
65
Содержание SuperDrive ACS24 Series
Страница 12: ......
Страница 34: ......
Страница 38: ......
Страница 79: ...26 04 2005 Troubleshooting guide User s Guide 1 0 Item No 89Y05120A 79...
Страница 81: ...26 04 2005 Troubleshooting guide User s Guide 1 0 Item No 89Y05120A 81...
Страница 82: ...Troubleshooting guide 26 04 2005 Item No 89Y05120A User s Guide 1 0 82...
Страница 86: ...Troubleshooting guide 26 04 2005 7 7 11 CAN TIME OUT Error Code 0x8100 Item No 89Y05120A User s Guide 1 0 86...
Страница 92: ......