Matrix PS System Installation and Commissioning Guide
|
73
Dali Wireless Proprietary and Confidential | DW-MAN-036 Rev 06
6.2
Preparing for Installation
Before installing the unit, become familiar with the following installation workflow, power
consumption, and warnings.
For FCC compliance and Safety Information, see the FCC statements at the beginning
of this document.
6.2.1
Power Consumption
The maximum power consumption of the type 2 unit is 340 W. For thermal load and
power consumption details per RF module, see
6.2.2
Input Power Requirements
The units have the following input power requirements:
Power supply cables with a minimum temperature rating of 65° C
Building power input protection of maximum 28 A
6.2.3
Warnings
This equipment is to be installed in a Restricted Access Area.
When installed in a wet, outdoor area, turn power off prior to
unit modifications.
This equipmnet is considered a permanently connected device. A
readily accessible disconnect device shall be incorporated
external to the equipment.
6.2.4
Weight
No. RF Modules
Weight
4
59.5 lbs (27 kg)
6.2.5
Remote Orientation
Do not mount the remote in a horizontal or an inverted vertical orientation, as this will
impair fan operation and reduce the operational temperature range. Contact Dali
Customer Service for more information.