18.1.2 Refrigerant piping material
▪
Piping material:
phosphoric acid deoxidised seamless copper
▪
Flare connections:
Only use annealed material.
▪
Piping temper grade and thickness:
Outer diameter (Ø)
Temper grade
Thickness (t)
(a)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
Annealed (O)
≥0.80 mm
t
Ø
15.9 mm (5/8")
Annealed (O)
≥0.99 mm
19.1 mm (3/4")
22.2 mm (7/8")
Half hard (1/2H)
≥0.80 mm
28.6 mm (1 1/8")
Half hard (1/2H)
≥0.99 mm
(a)
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
18.1.3 Refrigerant piping insulation
▪
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
▪
Insulation thickness:
Ambient temperature
Humidity
Minimum thickness
≤30°C
75% to 80% RH
15 mm
>30°C
≥80% RH
20 mm
18.1.4 To select the piping size
Determine the proper size using the following tables and reference figure (only for
indication).
B
A
B
c
e
C
C
D
D
d
b
3
C'''
D
D
d
a
10
a
11
a
1
a
2
a
3
a
4
a
5
a
6
a
7
a
8
a
9
D
D
d
C'
D
D
C''
C
b
1
D
D
D
b
2
a1~a11
VRV DX indoor units
b1~b3
SV units
c
First indoor branch kit (header)
d
Indoor branch kit (refnet)
e
Outdoor multi connection kit
Содержание VRV 5 RXYA8A7Y1B
Страница 197: ......
Страница 198: ......
Страница 199: ......
Страница 200: ...4P749918 1 2023 12 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...