24
|
Maintenance and service
Installer and user reference guide
172
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
24 Maintenance and service
NOTICE
Maintenance MUST be done by an authorised installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
In this chapter
About service mode operation............................................................................................................................................... 173
24.3.1
24.1 Maintenance safety precautions
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
WARNING
Prior to start working on systems containing flammable refrigerant, safety checks are
necessary to ensure that the risk of ignition is minimised. Therefore, some
instructions should be followed.
Please refer to the service manual for more information.
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in
order to eliminate static electricity and to protect the PCB.
24.1.1 To prevent electrical hazards
When performing service to inverter equipment:
1
Do NOT open the switch box cover for 10 minutes after turning off the power
supply.