Charging refrigerant
Installer and user reference guide
119
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
Model
Parameter C
SV8A
0.9 kg
Metric piping.
When using metric piping, replace the weight factors in the formula
by the ones from the following table:
Inch piping
Metric piping
Piping
Weight factor
Piping
Weight factor
Ø6.4 mm
0.020
Ø6 mm
0.016
Ø9.5 mm
0.053
Ø10 mm
0.058
Ø12.7 mm
0.10
Ø12 mm
0.088
Ø15.9 mm
0.16
Ø15 mm
0.14
Ø16 mm
0.16
Ø19.1 mm
0.23
Ø19 mm
0.22
Connection ratio requirements.
When selecting indoor units, the connection ratio
must comply with the following requirements. For more information, see the
technical engineering data.
Other combinations than those mentioned in the table are not allowed.
Indoor
units
Maximum
(a)
Total CR
(b)
Maximum total
indoor unit
capacity
CR per type
(c)
VRV DX
AHU
VRV DX
only
64
50~130%
650
50~130%
—
VRV DX +
AHU
64
50~110%
550
50~110%
0~60%
AHU only
—
75~110%
(d)
550
—
75~110%
(d)
(a)
Maximum number allowed excluding SV units and including EKEXVA kits
(b)
Total CR = Total indoor unit capacity connection ratio
(c)
CR per type = Allowable capacity connection ratio per indoor unit type
(d)
Additional restrictions might apply for connection ratio lower than 75% (65~110%). Please
refer to the EKEA+EKEXVA manual.