25
|
Troubleshooting
Installer and user reference guide
178
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
Main
code
Sub code
Cause
Solution
SVEO
(a)
SVS
(b)
Master Slave 1
The R32 sensor in one of the indoor
units has detected a refrigerant
leak
(c)
Possible R32 leak. The SV unit will
close the shut-off valves of the
branch pipe port to which the
corresponding indoor unit is
connected. Indoor units on this
branch pipe port will be out of
operation until the leak is repaired.
In case the indoor unit is directly
connected to the outdoor unit, the
compressor will shut down and the
unit will stop operating. Also all
shut-off valves for all ports in all SV
units in the system will be closed.
Refer to service manual for more
information.
The R32 sensor in one of the SV unit
has detected a refrigerant leak
Possible R32 leak. The SV unit will
close all of its shut-off valves and
triggers the ventilation system of
the SV unit. The system goes in
locked status. Service is needed to
repair the leak and activate the
system. Refer to the service manual
for more information.
/
Safety system error (leak detection)
(c)
An error related to the safety
system occurred.
Refer to the service manual for
more information.