21
|
Configuration
Installer and user reference guide
148
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
Code
Shows ...
[1‑18]
The 2nd last malfunction code
[1‑19]
The 3rd last malfunction code
When the latest malfunction codes were reset by accident on an indoor unit user
interface, they can be checked again through this monitoring settings.
For the content or reason behind the malfunction code see
176], where most relevant malfunction codes are
explained. Detailed information about malfunction codes can be consulted in the
service manual of this unit.
[1‑29] [1‑30] [1‑31]
Shows the result of the leak detection function.
Result
Description
No data
Leak detection failure due to abnormal operation
No leak detected
Leak detected
For instructions on how to use the leak detection function, see
[1‑34]
Shows the remaining days until the next automatic leak detection (if automatic leak
detection function is activated).
When the automatic leak detection function was activated through mode 2
settings, it is possible to see within how many days, the automatic leak detection
will be performed. Depending on the chosen field setting, the automatic leak
detection function can be programmed one time into the future or on perpetual
basis.
Indication is given in remaining days and is between 0 and 365 days.
[1‑40] [1‑41]
Code
Shows ...
[1‑40]
The current cooling comfort setting
[1‑41]
The current heating comfort setting
See
"21.2 Energy saving and optimum operation"
156] for more details about
this setting.
21.1.8 Mode 2: field settings
Cool/Heat selection setting.
Cool/Heat selection setting is used in case the optional Cool/Heat selector
(KRC19-26A and EKBRP2A81) is used. Depending on the outdoor unit setup (single
outdoor unit setup or multi outdoor unit setup), the correct setting should be
chosen. More details on how to use the Cool/Heat selector option can be found in
the manual of the Cool/Heat selector.