Special requirements for R32 units
Installer and user reference guide
75
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
The natural ventilation safety measure can be applied by following the steps
below:
Step 1
– Determine total room area, which is the total area of the space that has
natural ventilation
and
the space in which the indoor unit is installed:
The respective room area can be determined by projecting the walls, doors and
partitions to the floor and calculating the enclosed area. Spaces connected only
through false ceilings, ductwork, or similar connections are not considered a single
space.
Step 2
– Use the graph or table below to determine the total refrigerant charge:
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
5
0
25 30 35 40 45 50 55 60 65
20
15
10
70 75 80
m
[kg]
A
1
+ A
min
[m
2
]
A
1
+ A
min
[m²]
m
[kg]
20
6.7
30
10.1
40
0
0
10
3.3
13.5
50
16.8
60
20.2
70
23.6
80
27.0
90
30.3
100
33.7
110
37.1
120
40.5
130
43.9
140
47.2
150
50.6
160
54.0
170
57.4
180
60.7
190
64.1
200
67.5
210
70.9
220
74.2
230
77.6
236
79.6
237
79.8
240
79.8
250
79.8
m
Total refrigerant charge in the system [kg]
A
1
Area of the room with natural ventilation [m²]
A
min
Minimum room area of the space in which the indoor unit is installed [m²]
Note:
Round down the derived values.
The graphs and table are based on an installation height of the indoor unit
between 1.8 m and 2.2 m (bottom of indoor unit or bottom of duct openings).
If the installation height is more than 2.2 m, higher total refrigerant charge limit of
the system can apply. To know the total refrigerant charge limit of the system in
case the installation height is more than 2.2 m, refer to the online tool (
Step 3
– The total amount of refrigerant in the system MUST be less than the
refrigerant charge limit derived from the graph above. If NOT, natural ventilation
safety measure is not allowed.
Step 4
– The partition between two rooms on the same floor MUST meet one of
the following two requirements for natural ventilation.
1
Rooms on the same floor that are connected with a permanent opening that
extends to the floor and is intended for people to walk through.
2
Rooms on the same floor connected with permanent openings that fulfil the
requirements listed below. The openings must consist out of two parts to allow
air circulation for natural ventilation.