Charging refrigerant
Installer and user reference guide
124
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
19.9 To check refrigerant piping joints for leaks after charging refrigerant
Tightness test of field-made refrigerant joints indoors
1
Use a leakage test method with a minimum sensitivity of 5 g of refrigerant/
year. Test leaks using a pressure of at least 0.25 times the maximum working
pressure (see "PS High" on the unit nameplate).
If a leak is detected
1
Recover the refrigerant, repair the joint, and repeat the test.
2
"18.3.4 To perform a leak test"
112].
3
Charge refrigerant.
4
Check for refrigerant leaks after charging (see above).