Field Setting
Si71-812
84
Field Setting
1.
Field Setting
1.1
Field Setting and Test Run
1.1.1 Perform Field Settings with the Remote Controller
(1) Make sure the Electric Parts Box Lids are closed on the Indoor and Outdoor Units.
(2) Depending on the Type of Installation, make the Field Settings from the Remote
Controller after the Power is turned on, following the “Field Settings” Manual which
came with the Remote Controller.
Lastly, make sure the customer keeps
the “Field Settings” manual, along with
the operating manual, in a safe place.
Local setting
Using the remote controller of the VRV-system air conditioner to make HRV unit settings
<Initial setting>
•
Mode nos. 17,18 and 19: Group control of HRV units.
•
Mode nos. 27, 28 and 29: individual control
<Operating procedure>
The following describes the operating procedure and settings.
(1) Press the INSPECTION/TRIAL button for more than four seconds with the unit in the normal
mode to enter the local setting mode.
(2) Use the TEMPERATURE ADJUSTMENT button to select the desired “
Mode No.
”
(The code display will blink.)
(3) To make settings for individual units under group control (when mode No. 27, 28 or 29 is
selected), press the TIMER SETTING ON/OFF button to select the “
unit No.
” for which the
settings are to be made. (This process is not necessary when settings are made for the
entire group.)
(4) Press the top section of the TIMER button to select the “
FIRST CODE NO.
”
(5) Press the lower section of the TIMER button to select “
SECOND CODE NO.
”.
(6) Press the PROGRAM/CANCEL button once to enter the settings. (The code display will stop
blinking and light up.)
(7) Press the INSPECTION/TRIAL button to return to normal mode.
SETTING
Mode No.
SECOND
CODE NO.
FIELD
SET MODE
FIRST
CODE NO.
BRC1D527 (EU only)
BRC1A62
UNIT No.
GROUP
62
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...