Si71-812
Troubleshooting
Troubleshooting
77
2.21
Main Unit PC Board Assembly
Error Detection
Method
Check microcomputer operation monitor.
Error Generating
Conditions
When main unit PC board assembly does not operate.
When communication circuit errors.
Possible Causes
Fuse (excess current)
Power transformer
Noise
Main unit PC board
Troubleshooting
Main unit PC board (A1P)
NO
NO
NO
YES
Does equipment
reset properly.
Is it flashing?
After checking
other possible
causes, replace
PC board assembly.
Is monitor indicator
Off?
YES
YES
Monitor indicator remains
On.
With remote controller
disconnected, check
microcomputer operation
monitor.
Turn off power, then
restart.
Noise may be causing erroneous
operation. If power reset does not
solve the problem, replace main unit
PC board.
There may be a malfunction in main
unit PC board fuse, main unit PC board
or power transformer.
Check fuse and transformer. If they are
normal, replace PC board.
Replace main unit PC board.
(HF013)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
HAP
(HL031)
(Microcomputor Operation Monitor)
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...