Si71-812
Troubleshooting
Troubleshooting
81
2.24
Damper Motor
Error Detection
Method
Check damper motor and limit switch when damper motor does not operate.
Error Generating
Conditions
Possible Causes
Troubleshooting
Check resistance and voltage — DAMPER MOTOR
NO
YES
YES
Is
measured
value 0
Ω
when limit switch
turns on, and
infinity when
it turns
off?
Damper motor is
normal.
Place tester probes
at connectors of limit
switch, and check
continuity while
moving switch by
hand.
Limit switch is faulty.
Damper motor is faulty.
(HF017)
NO
Is
measured
value of EJ type
approx. 17 k
Ω
?
Place tester probes
on connectors of
damper motor and
check resistance.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(HL038)
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...