Troubleshooting
Si71-812
70
Troubleshooting
2.15
“
U5
”
Malfunction of Transmission between Remote
Controller and Indoor Unit
Remote
Controller
Display
U5
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer is signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Malfunction of indoor unit remote controller transmission
Connection of two main remote controllers (when using 2 remote controllers)
Defect of indoor unit PC board
Defect of remote controller PC board
Malfunction of transmission caused by noise
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2823)
NO
YES
YES
NO
Replace indoor unit PC
board.
Set one remote controller to
"SLAVE"; turn the power
supply off once and then back
on.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
NO
NO
Using
2-remote controllers
control.
All indoor
PC board microcomputer
monitors blink.
YES
Multi-core cable
is used for the indoor
unit remote controller
transmission
wiring.
Operation
returns to normal when
the power is turned off
momentarily.
YES
YES
SS1 of
both remote controllers
is set to "MASTER."
NO
Switch to double-core
independent cable.
replacement
Defect of remote controller PC
board or indoor unit PC board.
Replace whichever is
defective.
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...