Si71-812
Control Functions
Control Functions
51
1.1.6
External Damper Operation (FIELD SUPPLY)
Explanation of
Functions
Intake of outdoor air can be prevented when HRV is switched OFF if this damper is incorporated
in the system.
1. The total heat exchanger’s main unit print board supplies power for external damper.
Essential Wiring
1. Connect one end of the harness to the X15A on the print board and the other end to the
harness leading to the damper via a connector such as a closed connector.
With regard to closed connector, select one that suits wire diameter.
Note: Location of X15A: Refer to next page.
Essential Setting
Changes
The X15A output is at the default setting and is not in operation, so the output setting should be
changed at the LCD of the remote controller.
Setting changes should be made in the following way.
Mode No.: 18 (group tie up) or 28 (per each unit)
Setting switch No.: 3
Setting position No.: 03
In detail, refer to page 85.
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...