Troubleshooting
Si71-812
78
Troubleshooting
2.22
Thermistor
Error Detection
Method
Remove thermistor and check resistance with tester.
Error Generating
Conditions
Possible Causes
Faulty thermistor
Broken wire
Faulty control PC board
Faulty contact in connector
Troubleshooting
Note:
Refer to the thermistor temperature - resistance conversion table when measuring resistance.
NO
YES
Is
resistance
as shown below?
Thermistor is normal.
Remove thermistors
from main unit PC
board (A1P) (X12A,
X13A), and PC board
(A2P) (X13A, X14A,
X15A) check resistance
using tester.
If measured value deviates significantly
from values in the table, thermistor is
faulty.
(HF015)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.