Control Functions
Si71-812
48
Control Functions
1.1.2
Cold Area Mode
Stops or lowers ventilation airflow during defrosting operation and compressor non-operating
condition when equipment in heating mode, thus reducing heating load and cold air draft.
Operation chart (in heating operation only)
Note1:
Cold area mode can set using field setting mode of remote controller.
In detail, refer to page 85.
Note2:
During defrost operation, the fans of the unit continues driving (factory setting).
The purpose of this is to maintain the amount of ventilation and humidifying.
Though the fan can be stopped by the setting of the remote controller. In detail, refer to page 85.
Operation
By-pass
mode selection
Air conditioner
ON/OFF
Operation
Fan motor
Heat reclaim
v
entilation unit
Ventilation fan motor
Damper motor
(ventilation mode)
Total heat
exchange
mode
By-pass
mode
ON
OFF
ON
ON
Remote controller
indication
Operation lamp
Lamp
ON
(HL023)
Defrosting operation
or compressor in
non-operation
Non-defrosting operation or
compressor in operation
ON (Note 2)
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...