Troubleshooting
Si71-812
64
Troubleshooting
2.9
“
C4
”
Indoor Unit: Malfunction of Thermistor (R4T) for
Heat Exchanger
Remote
Controller
Display
C4
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defect of thermistor (R4T) for liquid pipe
Defect of indoor unit PC board (A2P)
Troubleshooting
∗
2: Refer to thermistor resistance / temperature characteristics table on P79.
(V2784)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the indoor unit PC board.
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R4T).
YES
YES
Connector
is connected to X12A
of the indoor unit PC
board.
Resistance
is normal when
measured after
disconnecting the thermistor
(R4T) from the indoor
unit PC board
(3.5k
Ω
~
360k
Ω
)
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...