Si71-812
Operation
Opration
19
1.4.3 Caution when Connecting the Indoor Unit Directly to the Duct
Follow the indications described below
a) When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as
with the outdoor unit, perform group-linked operation, and make the direct duct connection settings
from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Refer to
15.10.1 concerning setting method.
b) Do not connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure,
the unit might back up.
c) When it is connected to the suction side of indoor unit as a direct duct connection system, etc., since
there is a possibility that the body thermo of the indoor unit detects erroneously SA discharge from this
unit as indoor air, use the remote sensor (Optional).
EA
OA
RA
SA
Suction
grille
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...