Operating instructions
42
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
5
x
Parameter settings
5.13
Parameter levels for the EHS157068 mixer module
The parameter levels, parameter priorities, setting ranges and
associated functions are essentially the same as those described
in the preceding sections.
In some cases there exist at individual levels a restricted scope
of available parameters.
The description below relates only to the sections indicated.
Areas where there are significant differences are described in
greater detail.
Rotary switch setting: Info
See section 5.10.
If the assigned control unit is set to "Mix Valve #X", the displayed
values relate to the assigned heating circuit and to the compo-
nents connected to the EHS157068. (pump, mixer valve, ...).
When the assigned control unit is set to "Living Room", the
[T-Room adj] parameter is available. The rotary switch can be
used to change the room target temperature to the range
-5 K to +5 K. This function is not available if the control unit is
being used as a terminal function for remote control.
Rotary switch setting: Operating Mode
See section 5.4.
Rotary switch setting: Set Temp Day
See section 5.5.
Rotary switch setting: Set Temp Night
See section 5.6.
Rotary switch setting: DHW Set Temp
No function.
Rotary switch setting: DHW Install
No function.
Rotary switch setting: Time Program
See section 5.8.
Rotary switch setting: Configuration
See sections 5.13.1 and 5.13.2.
Rotary switch setting: Remote Param
See section 5.9.
5.13.1
Rotary switch setting: Configuration
, level "Setup"
Sub
-
lev
e
l
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Language
Language of the display text in the operating panel
E
E
Deutsch
English
French
Dutch
Italian
Spanish
Portuguese
Deutsch
1
Date
Current date in format day / month / year. The current day of the week is calculated
automatically from the date.
E
E
Time
Time in format hours / minutes.
E
E
Keylock Function
Release of the keylock function:
Off: Button block cannot be activated.
On: The button block can be activated using the rotary switch (see chapter 3.1).
E
E
Off
On
Off
-
Access Rights
Entering access code. Setting character by character like a combination lock
(see chapter 3.6.1).
E
E
0 - 9
0000
1
RoCon U1 assign
Display only on connected
room station:
Function of the EHS157034 room station in the data bus system:
Living Room: Control panel for the heating circuit assigned in the parameter [HC As-
signment].
Mixing Valve: Mixer circuit operating unit (as a mixer circuit extension or as a free-
standing mixer circuit controller)
Solar Module: Not applicable
In addition to the aforementioned functions, the room temperature controller can be ba-
sically used as a remotely controlled unit of the Daikin Altherma EHS(X/H) and the en-
tire RoCon system (with activated terminal function) (see chapter 4.2.2).
N
E
Living Room,
Mixing Valve,
Solar Module
Living Room
-
Master-RoCon
Display only on connected
room station:
Setting the caretaker function
Off: Deactivated
On: Function active
The caretaker function can be activated on any EHS157034 room station whose pur-
pose of use is set to "Living Room" and which is assigned to a heat generator (param-
eter [Boiler Assignment]> 0) (see chapter 4.2.2). Several room stations with active
caretaker function in the system are possible, however only one caretaker function is
possible per heat generator.
With the caretaker function active, all settings on the EHS157034 room station act in
the same way as the settings on the RoCon B1 for the assigned heat generator (may
differ from the control panel heating circuit assignment). As a result, the functions for
hot water preparation can also be remotely operated from the room station.
N
E
Off
On
Off
-
PWM Config
Min Perform Pump
Lower limit for modulation of the pump output
N
E
0 - 100 %
50 %
1 %
Max Perform Pump Upper limit for modulation of the pump output
N
E
0 - 100 %
100 %
1 %