Operating instructions
38
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
5
x
Parameter settings
5.5
Rotary switch setting: Set Temp Day
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-Room 1 Setpoint Target room temperature for the 1st switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0.5 °C
T-Room 2 Setpoint Target room temperature for the 2nd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0.5 °C
T-Room 3 Setpoint Target room temperature for the 3rd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0.5 °C
Tab. 5-7 Parameter in rotary switch setting "Set Temp Day"
5.6
Rotary switch setting: Set Temp Night
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-Reduced
Target room temperature for the setback times for the permanent timer programmes
[Automatic 1] and [Automatic 2].
E
E
5 - 40 °C
15 °C
0.5 °C
T-Absence
Target room temperature for the setback times for the temporary timer programmes [Away] and
[Vacation].
E
E
5 - 40 °C
15 °C
0.5 °C
Tab. 5-8 Parameter in rotary switch setting "Set Temp Night"
5.7
Rotary switch setting: DHW Set Temp
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-DHW Setpoint 1
Target hot water temperature for the 1st switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
10 - 70 °C
48 °C
1 °C
T-DHW Setpoint 2
Target hot water temperature for the 2nd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
10 - 70 °C
48 °C
1 °C
T-DHW Setpoint 3
Target hot water temperature for the 3rd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
10 - 70 °C
48 °C
1 °C
Tab. 5-9 Parameter in rotary switch setting "DHW Set Temp"