5.13.2
Rotary switch setting: Configuration
, level "Mixer Config"
Sensor Config
Outside Config
Configuration of the outside temperature sensor:
Off: Adoption of the outside temperature for the heat generator assigned to parameter
[Boiler Assignment] or no sensor evaluation
On: Sensor evaluation activates (if an outdoor temperature sensor is not connected to
the EHS157068 mixer module, an error message is generated.)
N
E
Off
On
On
-
Flow Temp Config
Configuration of the mixer circuit inflow temperature sensor:
Off: No sensor evaluation
On: Sensor evaluation activated (if no mixer circuit inflow temperature probe is con-
nected, a fault message is generated.)
N
E
Off
On
On
-
Outside Temp Adap Individual adapting for the measured value of the outdoor temperature relevant for the
Control.
N
E
-5.0 to +5.0 kW
0.0 K
0.1 K
Terminaladress
Setting the data bus address for system access. The set value must be applicable for
the entire system. Confirmation of this parameter using the rotary switch reinitialises
the controller.
N
E
Off, 0 - 9
Off
1
Boiler Assignment
Assignment of the EHS157068 to the heat generator, in accordance with the setting of
the [BUS ID HS] parameter (see section 5.12, tab. 5-14).
N
E
0 - 7
0
1
HC Assignment
Allocation of the EHS157068 control unit to the mixer module.
Off: If there is only one mixer module in the system this assignment is performed auto-
matically, otherwise the setting must match the address at the address switch for the
mixer module (see chapter 4.2.1, fig. 4-1).
0 - 9 = 0 - 9
10 = A
11 = B
12 = C
13 = D
14 = E
15 = F
N
E
Off, 0 - 15
Off
1
Tab. 5-15
Parameter in rotary switch setting "Configuration" level "Setup"
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
HC Function
Setting defines the type of inflow temperature control.
0: Weather-controlled flow temperature regulation
1: Regulating to a fixed set flow value, depending on the heating, cooling or setback mode
N
E
0 - 1
0
1
Pump Mode
Setting the operating mode of the mixer circuit pump.
0: Standard mixer circuit pump switching according to weather conditions / room temperature
1: Mixer circuit pump switching according to heating limits (optional room thermostat switch-
off also effective).
2: Mixer circuit pump switching according to heating programme
3: Mixer circuit pump in continuous running mode
N
E
0 - 3
0
1
T-Outside lim day
Only if parameter [Pump Mode] = 1:
Setting the automatic summer shutdown of the heating system. If the outside temperature
measured and averaged out by the controller exceeds the set value by 1 K, the heating cir-
cuit is switched off. The heating is enabled again once the outside temperature falls below
the set heating curve.
E
E
Off, 10 - 40 °C
19 °C
0.5 °C
T-Outside lim night
Only if parameter [Pump Mode] = 1:
Parameter for setting the heating limit for switch-off of the heating circuit during economy
mode (functionality as for parameter [T-Outside lim day]).
E
E
Off, 10 - 40 °C
10 °C
0.5 °C
Heat-Slope
Only if parameter [HC Function] = 0:
Setting the heating curve. The heating curve reflects the dependence of the set inflow tem-
perature of the heating circuit on the outside temperature (see chapter 3.6.2).
E
E
0.0 - 3.0
0.5
0.1
Room Influence
Only if the room station
is connected and assigned to the heating circuit.
Setting of the impact the deviation of the room temperature measured by the EHS157034
from the actual set value (see chapters 3.4.3 and 3.4.4) has on the flow temperature.
Off: Exclusively weather-controlled flow temperature regulation
0: Purely weather-controlled flow temperature regulation, but internal heat recirculation
pump continues to run until the next heating cycle following a heat demand during the set-
back time.
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve) by the
set factor.
For example: If the measured temperature is 2 K below the set value, the set flow tempera-
ture is raised 2-times the set value.
E
E
Off, 0 - 20
Off
1
T-Room Adj
Only if the room station
is connected and assigned to the heating circuit.
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the EHS157034
from the actual temperature in the living area of this room be detected, the measured value
can be corrected by the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
T-Flow Day
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the heating time when in
operating mode: "Automatic 1", "Automatic 2", "Heating".
E
E
20 - 90 °C
40 °C
1 °C
T-Flow Night
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the setback time when in
operating mode: "Automatic 1", "Automatic 2", "Reducing".
E
E
10 - 90 °C
10 °C
1 °C
Max T-Flow
The inflow temperature determined for the heating circuit is limited to the maximum value set
here.
N
E
20 - 70 °C
50 °C
1 °C