Parameter settings
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Operating instructions
31
5
Parameter settings
5.1
Explanation of the parameter tables
The parameter tables listed in the sections 5.2 to 5.11 contain im-
portant information concerning all parameters that are available
in the individual rotary switch setting on the controller (1. menu
level, 2. menu level).
In addition to the parameter designations, the tables contain de-
tails for the setting ranges, factory settings, setting options or
setting step distances and brief function explanations.
In addition, they provide explanation of the access rights for the
operation of the controller. The following abbreviations are
available for appropriate characterisation:
BE
Access right for the operator
HF
Access permission with technician code
If different settings appear in the BF and HF columns, the
user must log in as a technician so as to be able to
access the parameter level to change the status set in
the HF column, (see chapter 3.6.1).
Status:
N
Not visible
E
Visible and configurable
S
Visible
5.2
Rotary switch setting: Configuration
5.2.1 Level "Setup"
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Language
Language of the display text in the operating panel
E
E
Deutsch
English
French
Dutch
Italian
Spanish
Portuguese
Deutsch
1
Date
Current date in format day / month / year. The current day of the week is calculated au-
tomatically from the date.
E
E
Time
Time in format hours / minutes.
E
E
Keylock Function
Release of the keylock function:
Off: Button block cannot be activated.
On: The button block can be activated using the rotary switch (see chapter 3.1).
E
E
Off
On
Off
-
Access Rights
Entering access code. Setting character by character like a combination lock
(see chapter 3.6.1).
E
E
0 - 9
0000
1
RoCon U1 assign
Display only on connected
room station:
Function of the EHS157034 room station in the data bus system:
Living Room: Control panel for the heating circuit assigned in the parameter [HC Assign-
ment].
Mixing Valve: Mixer circuit operating unit (as a mixer circuit extension or as a free-stand-
ing mixer circuit controller)
Solar Module: Not applicable
In addition to the aforementioned functions, the room temperature controller can be ba-
sically used as a remotely controlled unit of the Daikin Altherma EHS(X/H) and the entire
RoCon system (with activated terminal function) (see chapter 4.2.2).
N
E
Living Room,
Mixing Valve,
Solar Module
Living
Room
-
Master-RoCon
Display only on connected
room station:
Setting the caretaker function
Off: Deactivated
On: Function active
The caretaker function can be activated on any EHS157034 room station whose purpose
of use is set to "Living Room" and which is assigned to a heat generator (parameter [Boil-
er Assignment]> 0) (see chapter 4.2.3). Several room stations with active caretaker func-
tion in the system are possible, however only one caretaker function is possible per heat
generator.
With the caretaker function active, all settings on the EHS157034 room station act in the
same way as the settings on the RoCon B1 for the assigned heat generator (may differ
from the control panel heating circuit assignment). As a result, the functions for hot water
preparation can also be remotely operated from the room station.
N
E
Off
On
Off
-
Outdoor type
Type exterior heat pump unit
0: No selection
1: 4 kW
2: 6 kW
3: 8 kW
4: 11 kW
5: 14 kW
6: 16 kW
N
E
0 - 6
0
1
INDOOR UNIT
Type of interior heat pump unit
0: So far no commissioning has taken place.
1: 304 - EHSX(B)04P30A
2: 308 - EHSX(B)08P30A
3: 508 - EHSX(B)08P50A
4: 516 - EHSX(B)16P50A
N
E
0 - 4
0
1