Operating instructions
30
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
4
x
Initial start-up
B: Configuration for setting "Mixing Valve"
●
Confirm the setting "Mixing Valve" by briefly pressing the
rotary switch.
The setting for the [HC Assignment] parameter is dis-
played.
●
Use the rotary switch to set the [HC Assignment] parameter.
This parameter must be identical with the data bus address of
the mixer module which is assigned to the EHS157034 room
station
.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the [Terminaladress] parameter is dis-
played.
●
Use the rotary switch to set the [Terminaladress] parameter.
This parameter defines the data bus address of the
EHS157034 room station
in the selected heating circuit.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the [Boiler Assignment] parameter is dis-
played.
●
Use the rotary switch to set the [Boiler Assignment]
parameter. This parameter defines the assignment of the
EHS157034 room station
to a Daikin Altherma EHS(X/H) in
the RoCon system.
Standard display is shown (see fig. 4-3).
The data bus address of the mixer module is set to the
address switch of the mixer (see fig. 4-1).
Make sure not to assign a duplicate value as the setting
of the [Terminaladress] parameter.
1
Display date
2
Status display: Screed func-
tion active
3
Status display: Technician
login
4
Display time
5
Current inflow temperature
of the mixer circuit
6
Current outside temperature
7
Operating mode setting for
the assigned heating circuit
Fig. 4-4
Standard display EHS157068 - "Mixing Valve" with example
of the status displays
In the setting "Mixing Valve" the indoor sensor of the
EHS157068 is deactivated.
4.2.3 Caretaker function
The caretaker function can be assigned to any EHS157034 room
station set
to "Living Room".
If more than one EHS157034 room stations are assigned to the
same heat generator, the caretaker function can only be as-
signed to one of them.
●
Enter the technician code (see chapter 3.6.1).
The
"Setup"
level is displayed after entering.
●
Select the [
Master-RoCon
] parameter using the rotary
switch.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the parameter is displayed.
●
Using the rotary switch, set the parameter for the function to
"On"
and confirm by pressing it quickly.
All settings
on
the
EHS157034
room station
act in the same
way as
settings on the
RoCon B1
control panel for the assigned
heat generator.
As a result, the functions for hot water preparation can also be
remotely operated from the room station.