Operating instructions
16
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
3
x
Operation
Assign the terminal address of the Daikin Altherma
EHS(X/H) to the control element RoCon B1
If several items of equipment in the RoCon system are
connected via the data bus, make sure not to duplicate
the setting of any parameters [Terminaladress].
●
Enter the expert code (see section 3.6.1).
The
"Setup"
level is displayed after entering.
●
Select the parameter [Terminaladress] with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
●
Within the display, use the rotary switch to set the unique
terminal address.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 5.2.1.
Activating / deactivating normal operation
Requirement: A valid terminal address is assigned to the
RoCon B1 control element of the Daikin Altherma EHS(X/H) or
the EHS157034 room station.
For setting the terminal address of optional connected
equipment, see chapter 4.2 or the instruction handbook
supplied for the respective equipment.
●
Place the rotary switch in
the
"Remote Param"
position.
The level "
Remote
Param
" is displayed.
●
Select the parameter
[Bus - Scan] with the
rotary switch.
●
Confirm the changes with
a brief push of the rotary
switch.
The context menu is
displayed.
Remote Param
Bus - Scan
No selection
Fig. 3-10 Display of the level
"Remote Param" at com-
missioning or temporary
disconnection from the
mains
●
Use the rotary switch to select the parameter [New scan?]
and confirm with "Yes".
Bus - Scan is performed.
An overview of all the equipment found is displayed.
●
Use the rotary switch to select the equipment for which the
terminal function is to be performed.
●
Confirm the changes with a brief push of the rotary switch.
The local control element acts as the remote control for
the external equipment.
To
end
terminal mode
and restore operation of the assigned
equipment to the control element, at the
level "
Remote Param
"
the
parameter [No selection]
must be selected and acknowl-
edged
(see fig. 3-10).
3.4.10 Quite Mode
Quite Mode means that the exterior heat pump unit is operating
at reduced output. This reduces the operating noise caused by
the exterior heat pump unit.
CAUTION!
Active Quite Mode reduces the performance in room
heating and room cooling operation with the result that
it may no longer be possible to reach the preset target
temperatures.
●
With outside temperatures below freezing, there is
a risk of material damage caused by frost.
The Quite Mode is set and turned off as follows:
●
Place the rotary switch in the
"Configuration"
position.
An overview is displayed.
●
Select the
"System Configuration"
level with the rotary switch.
An overview is displayed.
●
Select the parameter [Quite Mode] with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the parameter is displayed.
●
Setting parameters
– Parameter [Quite Mode] = 0: Deactivated
– Parameter [Quite Mode] = 1: Permanently activated
– Parameter [Quite Mode] = 2: Only activated at night
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this function can be seen
in chapter 5.2.2.
3.4.11 SMART GRID
WARNING!
There is a danger of scalding at target hot water tem-
peratures over 60 °C. This is possible as the electric
utilities company (EVU) is entitled to control the elec-
tricity consumption optimally in accordance with sup-
ply and demand in the SMART GRID regulations.
Due to the forced charging, the target hot water tem-
perature in the hot water storage tank can reach over
60 °C.
This storage tank charging even takes place when the
"Standby" operating mode it set.
●
Fit a scald-protection in the hot water distributor
line (e.g. VTA32 + Screw connection set 1" ).
You will need a special electric meter with an SG receiver for this
function, and the Daikin Altherma EHS(X/H) must be connected
to it.
As soon as the function is activated by the parameter [SMART
GRID] = 1, the heat pump is moved to the standby, normal or hot
water operating mode, depending on the signal provided by the
energy supply company.