 Parameter settings

Daikin RoCon HP 
Daikin Control
008.1420844 – 05/2014

Operating instructions

41

5.11 Exit button: Sonderfunktion

Parameter

Description

Access

Setting range

Min / Max

Factory 

setting

Increment

BE

HF

Manual Operation

The direct heating circuit and the target hot water temperature are controlled according to the 
temperature set in this parameter (see chapter 3.5.1).

E

E

20 - 80 °C

50 °C

1 °C

FA failure

Display of a current heat pump malfunction in the Daikin Altherma EHS(X/H). 

If "----" is displayed there is no fault (see chapter 6).

E

E

-

-

-

Protocol

Display of protocol (error and information messages). Here we display the saved messages of 
the Daikin Altherma EHS(X/H) and the connected data bus units with date a code, in each case 
as a menu item. By selecting an entry with the rotary switch, all other corresponding information 
is displayed concerning the selected fault message:
- Date and time of the message
- Code number (see chapter 6)
- Location (device) where the message originated
- Bus identification (device) where the message originated

E

E

-

-

-

Delete message

By setting this parameter to "On" and briefly pressing the rotary switch all the entries of the pro-
tocol, including the faults from connected data bus devices, are deleted.

E

E

Off
On

Off

-

RoCon B1/U1 Reset Resets all parameter settings to factory setting. Necessary for software updates. Complete re-

configuration subsequently required.

N

E

Off
On

Off

-

Parameter Reset

Resets all customer-specific parameter settings to factory setting.

N

E

Off
On

Off

-

Timeprog Reset

Resets all permanent time programmes to factory setting (see tab. 3-9).

E

E

Off
On

Off

-

Return

This parameter is used only to exit the special level.

E

E

Tab. 5-13 Parameter in the level "Sonderfunktion"

5.12 Parameter level "Basic Configuration"

This parameter level appears only if:
– At initial commissioning, if the query "use standard configura-

tion?" is answered by "No", or

– After, in the rotary switch position 

"Configuration" 

, level 

"Setup"

 the parameter [System Config] has been set to "inac-

tive" or "delete".

Parameter

Description

Access

Setting range

Min / Max

Factory 

setting

Increment

BE

HF

Boiler Function

Setting the system functionality of the device in the CAN-BUS. The standard value of this pa-
rameter is Single and thus applies to a Daikin Altherma EHS(X/H) in self-contained operating 
mode.
With value settings "Slave 1" to "Slave 8" the Daikin Altherma EHS(X/H) works as a heater 
module and waits for the demand for an optional cascade regulator.
These settings are not currently usable.

N

E

Single,

Slave 1,

...

Slave 8

Single

-

Unmixed Circ Config Setting the CAN-BUS-ID for the direct heating circuit. The data bus address of a heating circuit 

must be the same throughout the entire system. There must be no overlapping with the heating 
circuits in optional mixer circuits.

N

E

0 - 15

1

BUS ID HS

It is possible to operate up to 8 heat generators at the same time in single mode on the CAN 
Bus. This parameter can be used to set the unique differentiation of the necessary Bus detec-
tion. It is not possible to operate a Daikin Altherma EHS(X/H) in single mode in parallel with a 
cascade system.

N

E

0 - 7

1

Time Master

Activation of a system-wide time master. The time master synchronises all controllers in the 
Can system with the date and time set at the time master. The input of time and date can no 
longer be set at any other operating unit in the system. There may be only one time master in 
the entire system. The parameter is not available if the time master parameter is activated at a 
different controller in the CAN system.

N

E

Off
On

On

-

System Config

The system configuration of the unit, consisting of the sensor configuration and bus configura-
tion, can be deleted, activated and deactivated with this parameter. If you answer "yes" to the 
enquiry about using the standard configuration when starting the unit for the first time, the sys-
tem configuration will be activated automatically (see section 5.2.1, tab. 5-1).

N

E

Inactive;

Active.

Delete

Inactive;

-

Tab. 5-14 Parameter in the level "Basic Configuration"

Содержание RoCon HP

Страница 1: ...Operating instructions Daikin RoCon HP EHS157034 EHS157068 Daikin Control RoCon HP EHS157034 EHS157068 Operating instructions Daikin Control RoCon HP EHS157034 EHS157068 English...

Страница 2: ...irculation pump 27 3 6 16 Remote control via Internet 27 4 Initial start up 28 4 1 Starting up the Daikin Altherma EHS X H 28 4 2 Connect the optional RoCon devices and start them up 28 4 2 1 Starting...

Страница 3: ...rning can lead to damage to property and the environment This symbol identifies user tips and particularly useful information but not warnings or hazards Special warning signs Some types of danger are...

Страница 4: ...Daikin RoCon HP may only operated only according to the indications in this manual Any other use outside the intended use is considered as im proper The operator alone shall bear responsibility for an...

Страница 5: ...used to carry out different control functions in conjunction with external devices demand from an external heat generator switching to bivalent operating mode external status display etc In addition i...

Страница 6: ...ements 3 2 1 Display All the operating steps are supported by appropriate displays in the clear text display on a coloured background Menu guiding is available in 7 different languages see section 3 4...

Страница 7: ...rm accept selection and execute the function Tab 3 3 Functions of the rotary switch 2 3 Temporary timer programme Away active see section 3 4 7 2 3 Temporary timer programme Holiday active see section...

Страница 8: ...ally shows the standard display with rotary switch position In the first commissioning the setting for language selection is displayed first Select the language using the rotary switch Confirm the cha...

Страница 9: ...n the Info position Standard display is shown see fig 3 2 Press the rotary switch briefly The parameter overview is displayed Select the desired information level with the rotary switch Confirm the ch...

Страница 10: ...be changed by the heating technician If the water pressure falls below the minimum value set parameter value it must be increased by topping up the system see installation instructions of the Daikin...

Страница 11: ...bove the frost protection limit In the Standby operating mode the heat pump and any optionally connected backup heaters are isolated from the power supply Energy saving mode when the following conditi...

Страница 12: ...setting Note DHW Install DHW Install Section 3 4 6 Party Time Program Section 3 4 7 Away Holiday Vacation Screed Configuration HC Configuration Section 3 6 13 Only with expert code Tab 3 7 Overview o...

Страница 13: ...itching time program Various different timer programmes are available that are set in the factory but which can be adjusted to suit to provide conven ient and individual room and hot water temperature...

Страница 14: ...mme see also tab 3 8 1 timer programme for one optionally connected circula tion pump with 3 individual possible switching cycles Circulation Time The setting and input structure of the timer programm...

Страница 15: ...ionally connected components in the rotary switch setting Configuration Depending on access authority user or expert various different parameters are available Certain parameters are only acces sible...

Страница 16: ...he control element at the level Remote Param the parameter No selection must be selected and acknowl edged see fig 3 10 3 4 10 Quite Mode Quite Mode means that the exterior heat pump unit is operating...

Страница 17: ...to be started with the rotary switch Confirm the changes with a brief push of the rotary switch The selected programme starts Cancellation and jump back by pushing the exit button again or briefly act...

Страница 18: ...thermostat On or parame ter Interlink fct On the overheat protection switch must be connected so that the switching contact of the room thermostat is interrupted If the underfloor heating system is al...

Страница 19: ...system by conden sation Before initial commissioning and activation of cooling operation set the maximum permissible system temperature in the minimum temperature limit in the Control RoCon HP paramet...

Страница 20: ...eating circuit as a a Mixer extension The outside temperature determined by the outside temperature sensor connected to the Daikin Altherma EHS X H is transmitted to the mixer module via the CAN bus o...

Страница 21: ...get temperature normal inflow target temperature value of parameter T Flow CH adj Priority if both switch ing contacts are closed c Cooling operating mode active Closed switching contact heating IL1 T...

Страница 22: ...of use The minimum value THZUmin is calculated as follows THZUmin current active target hot water temperature T DHW Setpoint parameter TDiff DHW CH Support Switch on condition Tdhw THZUmin 4 K and Td...

Страница 23: ...Select the Air Purge parameter using the rotary switch 3 Confirm the changes with a brief push of the rotary switch The setting for the parameter is displayed 4 Using the rotary switch set the parame...

Страница 24: ...el is displayed after entering 2 Press the exit button for at least 5 s Menu Special Level is displayed 3 Select the programme Reset with the rotary switch 4 Execute the programme by briefly pressing...

Страница 25: ...provided by the manufac turer The first heating up starts at a feed temperature of 25 C which must be maintained for a period of 3 days Then heating is carried out at the maximum flow temperature set...

Страница 26: ...65 C The steps are 1 C Day Factory setting Day Factory setting 1 3 25 C 10 19 55 C 4 7 55 C 20 40 C 8 25 C 21 25 C 9 40 C 22 26 Tab 3 11 Presettings Screed Program Press the Exit key briefly An overv...

Страница 27: ...ion pump operates according to its own timer programme b Together with a hot water timer programme The circulation pump is actuated in parallel with the operating periods of the hot water timer progra...

Страница 28: ...For greater lengths use larger cross section areas Commercially available junction boxes can be used for con nection of Can bus lines of several RoCon devices Ensure power cables sensor cables and dat...

Страница 29: ...e the rotary switch to set the desired operating function for the room station Living Room Operating function see a c d Mixing Valve Operating function see b Solar Module Currently not available Depen...

Страница 30: ...er see fig 4 1 Make sure not to assign a duplicate value as the setting of the Terminaladress parameter 1 Display date 2 Status display Screed func tion active 3 Status display Technician login 4 Disp...

Страница 31: ...Access Rights Entering access code Setting character by character like a combination lock see chapter 3 6 1 E E 0 9 0000 1 RoCon U1 assign Display only on connected room station Function of the EHS15...

Страница 32: ...contact closed standard tariff 1 NC contact switching contact closed off peak tariff N E 0 1 0 Room thermostat Configuration of a room thermostat connected to the port J16 on the Daikin Altherma EHS...

Страница 33: ...evaluation On Sensor evaluation activated if no pressure sensor is connected a fault message is generated N E Off On On Outside Temp Adap Individual adapting for the measured value of the outdoor temp...

Страница 34: ...ing support 4 When there is a malfunction 5 When sensor value TVBH 60 C 6 When the outdoor temperature parameter value Equilibrium Temp Heat pump continues to operate Parallel bivalence operation 7 Wh...

Страница 35: ...ow Normal Good Very Good low Screed Function for screed drying Off Deactivated On The flow temperature is regulated according to the set screed programme The day on which the screed function is activa...

Страница 36: ...e is interrupted the function pauses until it is performed successfully on the next day or until it is ended by setting the parameter to Off or by changing the current operating mode The hot water gen...

Страница 37: ...threshold hot water charging Setting of the temperature difference to which the temperature in the domestic hot water stor age tank compared to the current target hot water temperature T DHW Setpoint...

Страница 38: ...ge Min Max Factory setting Increment BE HF T Reduced Target room temperature for the setback times for the permanent timer programmes Automatic 1 and Automatic 2 E E 5 40 C 15 C 0 5 C T Absence Target...

Страница 39: ...nd Monday to Sunday E E See chapter 3 4 7 See tab 3 9 15 min DHW Program 1 In this menu we can parametrise the 1st timer programme for hot water generation 3 switching cycles with a resolution of 15 m...

Страница 40: ...e direct heating circuit is displayed in C S S 0 100 C 0 1 C T HC Setpoint The set temperature of the flow in the direct heating circuit is displayed in C S S 0 90 C 0 1 C Status HS pump The current s...

Страница 41: ...itch position Configuration level Setup the parameter System Config has been set to inac tive or delete Parameter Description Access Setting range Min Max Factory setting Increment BE HF Boiler Functi...

Страница 42: ...is calculated automatically from the date E E Time Time in format hours minutes E E Keylock Function Release of the keylock function Off Button block cannot be activated On The button block can be ac...

Страница 43: ...to heating programme 3 Mixer circuit pump in continuous running mode N E 0 3 0 1 T Outside lim day Only if parameter Pump Mode 1 Setting the automatic summer shutdown of the heating system If the out...

Страница 44: ...a cooling function Only if parameter HC Function 0 Setting to determine from which outdoor temperature the lowest cooling flow temperature T Flow Cooling max is stipulated setting condition operating...

Страница 45: ...us address of the unit causing the fault Fig 6 2 Display of a current error message heat pump fault 6 1 2 Read Protocol The Protocol can be read in the Special Level see fig 6 3 The last received mess...

Страница 46: ...T Info Overview Water Pressure T HS Sw Nr B1 U1 Sw Nr RTX RT Sw Nr Controller Info Sw Nr B1 U1 Sw Nr Controller Sw Nr RTX RT Fig 6 4 Software information of the controller components Operating instruc...

Страница 47: ...l in the heat exchanger Heat pumping process In a closed coolant circuit the coolant absorbs heat from the surrounding air Compressing this coolant results in a higher temperature which can then be tr...

Страница 48: ...t ____ C Time period On Off On Off On Off HC Program 1 Monday Tuesday Wednesday Thursday Friday Saturday Sunday HC Program 2 Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 8 1 Individual...

Страница 49: ...tching time programme 8 x Notes Daikin RoCon HP Daikin Control 008 1420844 05 2014 Operating instructions 49 8 2 Parameter Enter your parameter changes in the table below Rotary switch setting Paramet...

Страница 50: ...Operating instructions 50 Daikin RoCon HP Daikin Control 008 1420844 05 2014 8 x Notes 8 3 Other items...

Страница 51: ...ating mode 18 With weather dependent regulation 20 Information messages 41 45 L Language setting 15 Low tariff mains connection 47 M Malfunctions 45 Manual operation 17 Mixer module 20 28 N Normal ope...

Страница 52: ...008 1420844_08 05 2014 Copyright Daikin...

Отзывы: