Parameter settings
5.10 Rotary switch setting: Info
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Overview
Display of different current operating data (see chapter 3.4.1).
S
S
-
-
-
Water Pressure
The current water pressure is displayed in bar.
S
S
0 - 4 bar
-
0.1 bar
T-HS
The current temperature (TVBH) of the heat generator is displayed in °C.
S
S
0 - 100 °C
-
1 °C
T-HS Setpoint
The current Inflow target temperature of the heat generator is displayed in °C
(see chapter 3.6.4).
S
S
0 - 90 °C
-
0.1 °C
T-Outside
The current external temperature is displayed °C.
S
S
-39 to +50 °C
0.1 °C
T-DHW
The current temperature of the hot water storage tank is displayed in °C. If there is no hot water
function activated, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C
T-DHW Setpoint
The current target hot water temperature is displayed °C. If there is no hot water function acti-
vated, "- - -" is displayed. The current set value is here always the maximum value of all rele-
vant demands for this hot water circuit.
S
S
10 - 70 °C
-
0.1 °C
T-Return
The current return flow temperature of the heat generator is displayed in °C. If there is no rel-
evant sensor connected to the heat generator, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C
Flow Rate
The filtered value of the current volume flow in litres per hour is displayed.
S
S
0 - 5100 l/h
-
l/h
T-HC
The inflow temperature in the direct heating circuit is displayed in °C.
S
S
0 - 100 °C
-
0.1 °C
T-HC Setpoint
The set temperature of the flow in the direct heating circuit is displayed in °C.
S
S
0 - 90 °C
-
0.1 °C
Status HS pump
The current status of the internal heat circulation pump in the Daikin Altherma EHS(X/H) is dis-
played.
S
S
Off
On
-
-
Runtime Compres-
sor
The running time of the refrigerant compressor is displayed in h.
S
S
-
-
h
Runtime Pump
The running time of the internal heating circulation pump is displayed in h.
S
S
-
-
h
Mixer Position
The current position of the 3UV DHW 3-way switch valve is displayed.
0 %: Position A (room heating)
100 %: Position B (domestic hot water generation)
S
S
0 - 100 %
-
1 %
Qboh
The amount of heat in the additional heat generator for hot water generation is displayed in
kWh.
S
S
-
-
kWh
Qchhp
The amount of heat in the additional heat generator for heating mode is displayed in kWh.
S
S
-
-
kWh
Qsc
The quantity of heat in the heat pump for cooling is displayed in kWh.
S
S
-
-
kWh
Qch
The quantity of heat in the heat pump for heating is displayed in kWh.
S
S
-
-
kWh
QWP
The total amount of heat in the heat pump is displayed in kWh.
S
S
-
-
kWh
Qdhw
The quantity of heat for hot water generation is displayed in kWh.
S
S
-
-
kWh
HS type
The heat generator type Daikin Altherma EHS(X/H) detected is displayed.
S
S
-
-
-
Sw Nr B1/U1
The software and version of the RoCon B1 operating unit is displayed.
S
S
-
-
-
Sw Nr Controller
The software number and the version of the RoCon BM1 circuit board are displayed.
S
S
-
-
-
Sw Nr RTX RT
The software number and the version of the RTX-AL4 circuit board are displayed.
S
S
-
-
-
Tab. 5-12 Parameter in rotary switch setting "Info"