Si39-406
Test Operation
General Information
69
4.4.1.2 Setting Contents and Code No.
– VRV Unit
Notes:
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however cannot
be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions the
indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the normal
mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
VRV
system
indoor
unit
settings
Mode
No.
Note 2
Setting
Switch
No.
Setting Contents
Second Code No.(Note 3)
01
02
03
04
10(20)
0
Filter contamination heavy/
light (Setting for display time to
clean air filter)
(Sets display time to clean air
filter to half when there is
heavy filter contamination.)
Super
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200
hrs.
Approx.
100
hrs.
1
Long life filter type
Long life filter
Super long life
filter
—
—
2
Thermostat sensor in remote controller
Use
No use
—
3
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)
Display
No display
—
12(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Indoor unit
turned ON by
thermostat
Operation output
Malfunction
output
1
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Forced OFF
ON/OFF control
—
—
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
1°C
0.5°C
—
—
3
OFF by thermostat fan speed
LL
Set fan speed
—
—
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
01:0
02:1
03:2
04:3
05:4
06:5
07:6
08:7
5
Power failure automatic reset
Not equipped
Equipped
—
—
13(23)
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.)
N
H
S
—
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
F (4 directions)
T (3 directions)
W (2 directions)
—
3
Air flow direction adjustment (Set at
installation of decoration panel.)
Equipped
Not equipped
—
4
Field set air flow position setting
Draft prevention
Standard
Ceiling Soiling
prevention
—
5
Field set fan speed selection
(fan speed control by air discharge outlet
for phase control)
Standard
Optional
accessory 1
Optional
accessory 2
—
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
2
Direct duct connection
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.)
∗
Note 6
Not equipped
Equipped
—
—
3
Drain pump humidifier interlock selection
Not equipped
Equipped
—
—
5
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—
6
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...