Si39-406
Installation
General Information
27
New Rank Compatible Flare Tool
Compared to previous refrigerants, the components of a HFC refrigerant is small. R410A also has a higher
pressure than other refrigerants. Therefore, in order to strengthen the intensity of the form and size of the flare
section used for R410A (class 2) apparatus, unlike the specification of the conventional refrigerants, it was set
up with different standards.
When carrying out flare processing, use a new rank compatible flare tool or a conventional flare tool.
Flare Gauge (Adapter Corresponding to the New Rank)
When using the later, use a flare gauge to take out the pipe from the gauge bar, adjust it, and then carry out the
flare processing.
Size from the dice surface to the copper tip (in mm)
(d) Coat the inner and outer surface of the flare with refrigerator oil (Ester or ether oil). (this ensures that the
flare nut passes smoothly, preventing the pipe from twisting.)
Do not use SUNISO-4GS oil.
Important points
1. Burrs should be carefully removed.
2. 2 spanners should be used to grip the flare nuts.
3. The flare nut must be inserted before starting the flaring operation.
4. The appropriate amount of torque should be used to tighten the flare nut.
5. Check that there is no superficial damage to the surface of the flare.
Name
Outer
diameter
mm
Wall
thickness
mm
Previous refrigerant (R22, R407C etc.)
R410A
The conventional flare tool
The conventional flare tool
Clutch type
Clutch type
1/4
6.35
0.8
0~0.5
1.0~1.5
3/8
9.52
0.8
0~0.5
1.0~1.5
1/2
12.70
0.8
0~0.5
1.0~1.5
5/8
15.88
1.0
0~0.5
1.0~1.5
Standard torques for tightening flare nut
±
10%
Size
Torque
ft. lbf
(kgf-cm)
(N-cm)
1/4(6.4
φ
)
10.4~12.7
144~176
1420~1720
3/8(9.5
φ
)
24.1~29.4
333~407
3270~3990
1/2(12.7
φ
)
36.5~44.5
504~616
4950~6030
5/8(15.9
φ
)
45.6~55.6
630~770
6180~7540
12mm×72mm
1.0×0.5mm Each
Flare gauge
Size
Thickness
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...