
Si39-406
Appendix
General Information
99
7. Appendix
7.1
Operating Noise of Indoor Units
7.1.1 Difference between Catalogue Data and Actual Noise
Operating noise differs depending on the place of measurement (room) because of the various
degrees with which the room reverberates the sound. To determine the amount of reverberation
under uniform conditions, the unit has been measured in a dead room with results having been
compiled in the below table. The actual sound produced in unit operation can be determined from
Table 1.
Sound pressure rise due to room reverberation (Higher than catalogue data)
Table 1
Classifications of indoor unit environments (reference data)
Table 2
Note:
1. Excluding bedrooms
2. Reference values of faint noises in the place of usage
A
B
C
Room Interior
Detection
Floor
Mortar
Linoleum tile
Carpet
Walls
Mortar
Plaster
Fibe
Saroncross finish
Ceiling
Mortar
mineral wool tile
Fibe
Saroncross finish
Average Absorbed Sound (Room with
Approx. 50 m² Floor Area)
0.05
0.12
0.25
Typical office
Estimated value to be added to
catalogue value
11~12
8~8.5
5~6
Classification
Environment
Example
Faint Noises
(NOTE 2)
Recommended
Operating Noise on Site
1
Non-active places requiring silence
Reception rooms, libraries, sitting rooms,
hospitals (examining rooms) (NOTE 1)
~35
~40
2
Sedate business activities that do not
disturb people even over time
Quiet offices, classrooms, small
conference rooms, lobbies
~40
~45
3
Somewhat quiet settings that permit soft-
spoken conversation, typical activities
Small offices, large conferences rooms,
quiet stores, restaurants
~45
~50
4
Somewhat loud settings that permit
regular conversation, brisk activity
Large offices, typical stores, cafeterias
~50
~55
5
Loud places that permit conversation in a
loud voice, highly active place with many
people
Loud large-side offices, large cafeterias,
loud stores
~55
~60
6
Rather loud settings
Factories, gymnasiums, recreational
places like pachinko parlors
~60
~65
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...