Si39-406
Refrigerant Piping
Installation Manual REYQ96MTJU
159
7. Field Wiring
CAUTION
All field wiring and components must be installed by a licensed electrician and must comply with
relevant local and national regulations.
The field wiring must be carried out in accordance with the wiring diagrams and the instructions
given below.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
This product's reversed phase protection detector only works when the product started up.
The reversed phase protection detector is designed to stop the product in the event of an
abnormalities when the product is started up.
Replace two of the three phases (L1, L2, and L3) during reverse-phase protection circuit operation.
Reversed phase detection is not performed while the product is operating.
If there exists the possibility of reversed phase after an momentary black out and the power goes
on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase can break the compressor and other parts.
7.1
Optional Parts
Note:
Use copper conductors only.
When using the adaptor for sequential start, refer to chapter “Examples”.
For connection wiring to outdoor-outdoor transmission F1-F2, outdoor-indoor transmission F1-
F2, refer to chapter “Examples”.
For connection wiring to the central remote controller, refer to the installation manual of the
central remote controller.
Use insulated wire for the power cord.
7.2
Power Circuit and Cable Requirements
A power circuit (see table below) must be provided for connection of the unit. This circuit must be
protected with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and
an earth leak detector.
When using residual current operated circuit breakers, be sure to use a high-speed type 200mA
rated residual operating current.
Note:
Select the power supply cable in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Phase and frequency
Voltage
Recommended fuses
REYQ96MTJU
φ
3, 60Hz
208-230V
70A
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...