Appendix
Si39-406
130
General Information
Main Points
When communications with the central remote controller are down, “00” cannot be selected in
the field setting mode.
Activate power to the central remote controller, unified ON/OFF controller and indoor unit before
setting the centralized control group number.
7.10.9 Example 9:
“
88
88
88
88
” cannot be cleared from the central remote controller
.
Situation
The display on the central remote controller does not change from its initial state after turning
power ON.
Initial display of the central remote controller
Cause
1. None of the indoor units connected to the central remote controller have been given a group No.
2. The connector for setting the master controller inside the central remote controller is
disconnected.
Remedial Action
Set a centralized control group No. for each indoor unit with the respective remote controllers.
Connect the connector for setting the master controller in one of the central remote controller.
Main Points
If the setting for master controller has been changed, reset the power to the unit at the ON/OFF
switch or the forced reset switch of the controller.
Activate power to the central remote controller, unified ON/OFF controller and indoor unit before
setting the centralized control group No.
For details on how to set the centralized control group number, refer to the installation manual.
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...