Test Operation
Si39-406
64
General Information
4.1.3 Check Operation
* During check operation, mount front panel to avoid the misjudging.
* Check operation is mandatory for normal unit operation.
(When the check operation is not executed, alarm code "U3" will be displayed.)
On completion of test operation, LED on outdoor unit PC board displays the following.
H3P ON: Normal completion
H2P and H3P ON: Abnormal completion
→
Check the indoor unit remote controller for
abnormal display and correct it.
In the case of multi-outdoor-unit system, make setting on the master unit PC board. (Setting with
the slave unit is disabled.)
[LED display in the case of multi-outdoor-unit system] (Same as that in emergency operation)
* Discriminate the operating status of the master unit/slave units through the following LED
display.
Malfunction code
In case of an alarm code displayed on remote controller:
Check on operation
(V3057)
Press and hold the TEST
OPERATION button (BS4) on
outdoor unit PC board for 5
seconds.
¡
The test operation is started automatically.
The following judgements are conducted within 15 minutes.
2
“Check for wrong wiring”
2
“Check refrigerant for over charge”
2
“Check stop valve for not open”
2
“Pipe length automatic judgement”
The following indications are conducted while in test operation.
2
LED lamp on outdoor unit PC board H2P flickers (test operation)
2
Remote controller Indicates “On Centralized Control” on upper
right.
Indicates “Test Operation” on lower left
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P H8P
(Factory set)
Master:
Slave 1:
Slave 2:
77
7777777
7777 7
7777777
7777777 9
9
7777777 7
7777777 7
Cause of trouble due to faulty
installation work
Alarm
code
Countermeasure
Closed stop valve of outdoor unit
E3
E4
F3
Liquid side stop valve : Open
Gas side stop valve : Open
Oil equalizing pipe stop valve : Close
Reversed phase in power cable
connection for outdoor unit
U1
Change connection of two wires among three for correct phasing.
Electric power for outdoor or indoor unit
is not supplied. (Including open phase)
U4
Check that the power cable for outdoor unit is connected properly.
Incorrect wiring between units
UF
Check that the wiring between units corresponds correctly to
refrigerant piping system.
Refrigerant overcharge
E3
F6
UF
Compute again optimum amount of refrigerant to be added based on
the piping length, then, collect the excessive amount by using
refrigerant collector to make the refrigerant amount proper.
Insufficient refrigerant
E4
F3
- Check that additional charging has been carried out.
- Compute again the refrigerant amount to be added based on the
piping length, and charge proper amount of refrigerant additionally.
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...