SiUS041829E
General Problem Symptoms and Check Items
Part 6 Service Diagnosis
65
1. General Problem Symptoms and Check Items
Symptom
Check Item
Measures
Reference
Page
The unit does not
operate.
Check the power supply.
Check if the rated voltage is supplied.
—
Check the type of the indoor unit.
Check if the indoor unit type is compatible with the
outdoor unit.
—
Check the outdoor temperature.
Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
Diagnose with remote controller
indication.
—
Check the remote controller
addresses.
Check if address settings for the remote controller
and indoor unit are correct.
Operation sometimes
stops.
Check the power supply.
A power failure of 2 to 10 cycles stops air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor temperature.
Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
Diagnose with remote controller
indication.
—
The unit operates but
does not cool, or does
not heat.
Check for wiring and piping errors in
the connection between the indoor
unit and outdoor unit.
—
—
Check for thermistor detection errors. Check if the thermistor is mounted securely.
—
Check for faulty operation of the
electronic expansion valve.
Set the unit to cooling operation, and check the
temperature of the liquid pipe to see if the
electronic expansion valve works.
—
Diagnose with remote controller
indication.
—
Diagnose by service port pressure
and operating current.
Check for refrigerant shortage.
—
Large operating noise
and vibrations
Check the output voltage of the power
module.
—
Check the power module.
—
—
Check the installation condition.
Check if the required spaces for installation
(specified in the installation manual) are provided.
—
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...