Check
Part 6 Service Diagnosis
117
Caution
Diagnose method (Diagnose according to 6 LEDs lighting status of the inverter analyzer.)
1. If all the LEDs are lit uniformly, the compressor is defective.
Replace the compressor.
2. If the LEDs are not lit uniformly, check the power module.
Refer to
Check No.22
.
3. If NG in
Check No.22
, the power module is defective.
Replace the main PCB. The power module is united with the main PCB.
If OK in
Check No.22
, check if there is any solder cracking on the PCB.
4. If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
1. When the output frequency is low, the LEDs blink slowly. As the output frequency increases, the
LEDs blink quicker. The LEDs look like they are lit.
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
5.8 Rotation Pulse Check on the Outdoor Unit PCB
Check No.16
Make sure that the voltage is within 320
VDC.
1. Set operation off and power off. Disconnect the connector S70 or S71.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 4 - 3 is 15 VDC.
4. Check that the rotation command voltage between the pins 4 - 2 is 0 ~ 6.5 VDC.
5. Keep operation off and power off. Connect the connector S70 or S71.
6. Check whether 4 rotation pulses (0 ~ 15 VDC) are input at the pins 4 - 1 when the fan motor is
rotated 1 turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2
Defective PCB
Replace the outdoor unit PCB (main PCB).
If NG in step 4
Defective Hall IC
Replace the outdoor fan motor.
If OK in both steps 2 and 4
Replace the outdoor unit PCB (main PCB).
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
+ 100
- 50
1
2
3
4
5
6
7
320 VDC
(R20507)
S70 or S71
PCB
Act
u
al rotation p
u
lse inp
u
t (0 ~ 15 VDC)
Rotation command voltage (0 ~ 6.5 VDC)
Control voltage 15 VDC
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...