SiUS041829E
Main Functions
Part 4 Functions and Control
27
1.5 Program Dry Operation
Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and
FAN
setting buttons are inoperable.
Details
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two zones.
Then, the unit operates in an appropriate capacity for each zone to maintain the temperature and
humidity at a comfortable level.
Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24°C or more
(75.2°F or more)
Room thermistor
temperature at start-up
X – 2.5°C
(X – 4.5°F)
X – 0.5°C
(X – 0.9°F)
18 ~ 23.5°C
(64.4 ~ 74.3°F)
X – 2.0°C
(X – 3.6°F)
X – 0.5°C
(X – 0.9°F)
17.5°C or less
(63.5°F or less)
18°C
(64.4°F)
X – 2.0°C
(X – 3.6°F)
X – 0.5°C = 17.5°C
(X – 0.9°F = 63.5°F)
Zone A = Thermostat OFF
Target temperat
u
re X
Zone B
Room temperat
u
re
Room temperat
u
re
Zone C = Thermostat ON
Y = X – 2.5
°
C (4.5
°
F)
or
Y = X – 2.0
°
C (3.6
°
F)
Z = X – 0.5
°
C (0.9
°
F)
X – 1.0
°
C (1.8
°
F)
(R24029)
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...