SiUS041829E
Main Functions
Part 4 Functions and Control
31
1.9 ECONO Operation
Outline
ECONO operation reduces the maximum operating current and the power consumption.
This operation is particularly convenient for energy-saving. It is also a major bonus when breaker
capacity does not allow the use of multiple electrical devices and air conditioners.
It can be easily activated by pressing
ECONO
button on the wireless remote controller.
Details
When this function is activated, the maximum capacity also decreases.
The remote controller can send the ECONO command when the unit is in cooling, heating, dry,
or automatic operation. This function can only be set when the unit is running. Pressing
ON/OFF
button on the remote controller cancels the function.
This function and POWERFUL operation cannot be used at the same time. The latest command
has the priority.
ECONO operation
(R22012)
Normal operation
Maxim
u
m d
u
ring normal operation
Maxim
u
m d
u
ring ECONO operation
Time
Power
cons
u
mption
and c
u
rrent
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...