Troubleshooting
SiUS041829E
94
Part 6 Service Diagnosis
Reference
Reference
Reference
Note
Troubleshooting
Check No.01
Check No.13
Check No.14
When replacing the defective thermistor(s), replace the thermistor as ASSY.
NG
OK
NO
OK
NG
OK
YES
NG
Correct the fo
u
r way valve
coil.
Reconnect the harness.
YES
YES
YES
NO
NO
Replace the o
u
tdoor
u
nit PCB (main PCB).
Replace the defective
thermistor(s).
Refer to the refrigerant line
check proced
u
re.
Replace the fo
u
r way valve
(defective or d
u
st-clogged).
Reconnect the
thermistor(s).
Caution
Be s
u
re to t
u
rn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R20405)
∗
Refrigerant shortage
∗
Water mixed
∗
Stop valve
Fo
u
r way valve
coil disconnected (loose)?
Harness
disconnected?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Check No. 13
Check the fo
u
r way valve
switching o
u
tp
u
t.
Check the contin
u
ity of the fo
u
r way
valve coil and harness.
Replace the fo
u
r way
valve coil.
NO
Resistance
between harnesses
abo
u
t 1000 ~ 2000
Ω
?
Disconnect the harness from the
connector.
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...