Check
SiUS041829E
112
Part 6 Service Diagnosis
5. Check
5.1 Thermistor Resistance Check
Check No.01
Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance between
the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6000517
M
u
ltimeter
Resistance range
Thermistor ASSY
Soldered thermistor
M
u
ltimeter
Thermistor temperature
Resistance (kΩ)
(°C)
(°F)
R (25°C (77°F)) = 20 kΩ
B = 3950 K
–20
–4
197.8
–15
5
148.2
–10
14
112.1
–5
23
85.60
0
32
65.93
5
41
51.14
10
50
39.99
15
59
31.52
20
68
25.02
25
77
20.00
30
86
16.10
35
95
13.04
40
104
10.62
45
113
8.707
50
122
7.176
(k
Ω
)
150
100
50
–15
0
15
30
45
(R14467)
5
32
59
86
113
(°C)
(°F)
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...