SiUS041829E
Troubleshooting
Part 6 Service Diagnosis
73
Reference
4.3 Freeze-up Protection Control/Heating Peak-cut Control
Error Code
A5
Method of Error
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Error Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 62.5°C (144.5°F).
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
Check No.01
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
(R21064)
YES
YES
NO
Caution
Provide s
u
fficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor
u
nit PCB
(control PCB).
Replace the indoor heat
exchanger thermistor.
As
described in the
thermistor characteristic
chart?
Check the air filter.
Check the d
u
st acc
u
m
u
lation on
the indoor heat exchanger.
Is there any short circ
u
it?
Dirty?
Dirty?
Check the air passage.
Be s
u
re to t
u
rn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...