SiUS041829E
Troubleshooting
Part 6 Service Diagnosis
93
4.15 Four Way Valve Abnormality
Error Code
EA
Method of Error
Detection
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Error Decision
Conditions
The following condition continues over 10 minutes after operating for 5 minutes.
Cooling/Dry
A
–
B
< –5°C (
A
–
B
< –9°F)
Heating
B
–
A
< –5°C (
B
–
A
< –9°F)
A
: Room thermistor temperature
B
: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...