Control Specification
SiBE06-708_A
47
Function and Control
3.3.2 Four Way Valve Switching
Outline
In heating operation, current is conducted, and in cooling and defrosting, current is not
conducted. In order to eliminate the switching sound when the heating is stopped, as the four
way valve coil switches from ON to OFF, the OFF delay switch of the four way valve is carried
out after the operation stopped.
Detail
OFF delay switch of four way valve:
The four way valve coil is energized for 150 ~ 160 seconds after the operation is stopped.
3.3.3 Four Way Valve Operation Compensation
Outline
At the beginning of the operation as the four way valve is switched, the differential pressure to
activate the four way valve is acquired by having output frequency which is more than a certain
fixed frequency, for a certain fixed time.
Detail
Starting Conditions
1. When starting compressor for heating.
2. When the operation mode changes to cooling from heating.
3. When starting compressor for defrosting or resetting.
4. When starting compressor for the first time after the reset with the power is ON.
5. When starting compressor for heating next to the suspension of defrosting.
6. When starting compressor next to the fault of switching over cooling / heating.
Set the lower limit frequency
Hz for
seconds with any conditions 1 through 6 above.
3.3.4 3-minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(Except when defrosting.)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
25/35 class
50 class
Cooling
Heating
Cooling
Heating
(Hz)
68
66
48
48
(seconds)
45
70
25/35 class
50 class
Unit
FCG 1
48
55
Hz
FCG 2
64
70
FCG 3
88
85
TCG 1
240
120
seconds
TCG 2
360
200
TCG 3
180
470
(sec.)
Time
(R10540)
FCG3
FCG2
FCG1
TCG1
TCG2
TCG3
(Hz)
Frequency