SiBE06-708_A
Troubleshooting
Service Diagnosis
102
Troubleshooting
Check No.04
Refer to P.127
Check No.06
Refer to P.129
Check No.07
Refer to P.130
Check No.08
Refer to P.130
Check No.09
Refer to P.131
(R11897)
Caution
Replace the fan motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 09
Check the outdoor fan.
Check No. 08
Check the discharge
pressure.
Check No. 04
Check the electronic
expansion valve.
Check No. 06
Check the outdoor heat
exchanger thermistor.
Check No. 07
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Floor Standing Type F-Series
Страница 12: ...SiBE06 708_A 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Cooling Only 2 1 2 Heat Pump 5 ...
Страница 19: ...SiBE06 708_A Specifications 8 Part 2 Specifications 1 Specifications 9 1 1 Cooling Only 9 1 2 Heat Pump 14 ...
Страница 146: ...Check SiBE06 708_A 135 Service Diagnosis RK X S25 35G2V1B9 models R12035 Tester 1 2 3 4 ...