SiBE06-708_A
Outdoor Unit - RK(X)S50F2V1B, RK(X)S50G2V1B
Removal Procedure
240
5.3
Removal of Electrical Box
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1
Remove the 2 screws
of the shield plate.
Preparation
Remove the top panel and
the front panel according to
the “Removal of Outer
Panels”.
2
Slide the shield plate
upward to unfasten the
1 hook on the bottom
left, and then remove
the shield plate.
3
Disconnect the 2 power
supply cables and the 1
earth wire.
(R5266)
Shield
plate
(R5267)
(R5268)
Earth wire