Outdoor Unit - RK(X)S25/35G2V1B9
SiBE06-708_A
213
Removal Procedure
4
Disconnect the relay
connector for the
compressor.
5
Disconnect the
connector for the
electronic expansion
valve coil [S20].
6
Cut the clamp.
7
Pull out the outdoor
heat exchanger
thermistor.
Be careful not to lose the clip
for the thermistor.
Step
Procedure
Points
(R11845)
(R11847)
[S20]
(R11850)
(R11851)
Outdoor heat
exchanger thermistor
Clip