![Daikin Floor Standing Type F-Series Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/daikin/floor-standing-type-f-series/floor-standing-type-f-series_service-manual_4065090101.webp)
SiBE06-708_A
Troubleshooting
Service Diagnosis
90
4.6
Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
Remote
Controller
Display
U4
Method of
Malfunction
Detection
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is
checked whether it is normal.
Malfunction
Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Defective indoor unit PCB
Disturbed power supply waveform
Troubleshooting
Check No.10
Refer to P.131
Check No.10
Check the power supply
waveform.
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
YES
YES
Replace the indoor unit PCB.
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
NO
(R12160)
NO
YES
YES
NO
NO
Caution
Correct the indoor unit-outdoor
unit connection wires.
Diagnose the outdoor unit
PCB.
∗
Before you check the LED A,
cancel the standby electricity
saving function by operating
fan operation with the remote
controller.
∗
Wait at least for 7 sec. after
turning on the power.
Replace the connection wires
between the indoor and
outdoor units.
Is LED A blinking?
Properly insulated?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit-outdoor unit
connection wires.
Check the LED A on the outdoor
unit PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Floor Standing Type F-Series
Страница 12: ...SiBE06 708_A 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Cooling Only 2 1 2 Heat Pump 5 ...
Страница 19: ...SiBE06 708_A Specifications 8 Part 2 Specifications 1 Specifications 9 1 1 Cooling Only 9 1 2 Heat Pump 14 ...
Страница 146: ...Check SiBE06 708_A 135 Service Diagnosis RK X S25 35G2V1B9 models R12035 Tester 1 2 3 4 ...