Outdoor Unit - RK(X)S25/35G2V1B
SiBE06-708_A
187
Removal Procedure
4
Disconnect the
connectors for the
magnetic relay [S50]
and for the thermistors
[S90].
5
Disconnect the
connectors for the filter
PCB [S10] and for the
overload protector
[S40].
6
Disconnect the
connectors for the
electronic expansion
valve coil [S20] and for
the four way valve coil
[S80].
Step
Procedure
Points
(R9341)
[S90] [S50]
(R9342)
[S40]
[S10]
(R9343)
[S80]
[S20]