Control Specification
SiBE06-708_A
57
Function and Control
3.13 Forced Operation Mode
Outline
Forced operation mode includes only forced cooling.
Detail
3.14 Standby Electricity Saving
RK(X)S25/35G2V1B, RK(X)S25/35G2V1B9 Models Only
This function turns power supply OFF to the outdoor unit and sets the indoor unit into energy-
saving mode, thus reducing the power consumption of the air conditioner.
Field setting is required for turning ON the function.
Refer to “Standby Electricity Saving” on page 259 for detail.
Item
Forced Cooling
Conditions
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced operation is allowed when the above both conditions are met.
Start
The forced operation starts when any of the following conditions is fulfilled.
1) Press the forced operation ON/OFF button (SW1) on the indoor unit for 5
seconds.
2) Press the forced operation ON/OFF button (SW1) on the outdoor unit.
(RK(X)S25/35G2V1B9 models only)
Command
frequency
RK(X)S25/35F2V1B, RK(X)S25/35G2V1B: 68 Hz
RK(X)S25/35G2V1B9: 58 Hz
RK(X)S50F2V1B, RK(X)S50G2V1B: 66 Hz
End
The forced operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced operation ON/OFF button (SW1) on the indoor unit again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced operation ON/OFF button (SW1) on the outdoor unit.
Others
The protection functions are prior to all others in the forced operation.
Содержание Floor Standing Type F-Series
Страница 12: ...SiBE06 708_A 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Cooling Only 2 1 2 Heat Pump 5 ...
Страница 19: ...SiBE06 708_A Specifications 8 Part 2 Specifications 1 Specifications 9 1 1 Cooling Only 9 1 2 Heat Pump 14 ...
Страница 146: ...Check SiBE06 708_A 135 Service Diagnosis RK X S25 35G2V1B9 models R12035 Tester 1 2 3 4 ...